SICK

UE45-3S13D33

SKU: 6024912 Discontinued
Price excluding VAT

Request a quote

    Safety relays | UE45-3S1 | UE45-3S13D33 | Applications: Evaluation unit | Compatible sensor types: Safety command devices, Safety switches | External device monitoring (EDM): Integrated | Supply voltage: 24 V DC | Off-delay time: 0.15 s 3 s | Number of enable current contacts: 3 | Housing width: 22.5 mm

    Safety integrity level
    1)
    Category
    Category 4 (EN ISO 13849)2)Category 3 (EN ISO 13849)1)
    Performance level
    PL e (EN ISO 13849)2)PL d (EN ISO 13849)1)
    B10dparameter
    4 x 105switching cycles (with maximum load)
    PFHD(mean probability of a dangerous failure per hour)
    3.0 x 10-8(EN ISO 13849)2)2.0 x 10-8(EN ISO 13849)1)
    TM(mission time)
    20 years (EN ISO 13849)
    Stop category
    0 (EN 60204-1)2)1 (EN 60204-1)1)
    Voltage supply
    A1, A2
    Output circuit ≤ 25 V AC / 60 V DC
    PELV or SELV
    Supply voltage Vs
    A1, A2
    Residual ripple
    (≤ 2.4 Vpp)1)
    Power consumption
    2.6 W (DC)
    Overvoltage category
    II
    Rated insulation voltage Ui
    300 V AC
    Rated impulse withstand voltage Uimp
    4 kV
    Test voltage
    2 kV (50 Hz) (EN 60439-1)
    Control voltage
    22 V DC
    Short-circuit current
    ≤ 2.2 A, between S 11 and A 2
    Short-circuit protection
    PTC resistor
    Manual
    (≤ 30 ms)
    Automatic
    (≤ 600 ms)
    Activation time of reset button
    ≤ 30 ms≤ 600 ms
    Synchronous time monitoring
    ≤ 500 ms
    Cable resistance
    ≤ 85 Ω
    Response time
    25 ms1)
    Off-delay time
    0.15 s ... 3 s
    Number of enabling current paths (N/O)
    2, category 4
    Number of off-delayed N/O contacts
    1, category 3
    Number of on-delayed N/O contacts
    Category 3
    Contact type
    Positively driven
    Contact material
    Silver alloy, gold flashed
    Enabling current path
    10 mA ... 6 A
    Total current
    ≤ 12 A
    Usage category
    AC-15/DC-13 (EN 60947-5-1)
    Rated operating current (voltage)
    4 A (230 V AC) 360 switching cycles/h4 A (24 V DC) 360 switching cycles/h2.5 A (24 V DC) 3600 switching cycles/h
    Switching frequency
    ≤ 3600/h
    Mechanical life (relay contacts)
    5 x 106switching cycles
    Electrical life (relay contacts)
    2 x 106switching cycles
    Dimensions (W x H x D)
    22.5 mm x 114 mm x 96.5 mm
    Contamination rating
    3 (EN 50178)
    Weight
    0.2 kg
    ECLASS 5.0
    27371990
    ECLASS 5.1.4
    27371990
    ECLASS 6.0
    27371819
    ECLASS 6.2
    27371819
    ECLASS 7.0
    27371819
    ECLASS 8.0
    27371819
    ECLASS 8.1
    27371819
    ECLASS 9.0
    27371819
    ECLASS 10.0
    27371819
    ECLASS 11.0
    27371819
    ECLASS 12.0
    27371819
    ETIM 5.0
    EC001449
    ETIM 6.0
    EC001449
    ETIM 7.0
    EC001449
    ETIM 8.0
    EC001449
    UNSPSC 16.0901
    41113704
    Download Datasheet

    Manuals, CAD models, certificates and other materials are available on the manufacturer's website: