    Pressure sensors | PAC50 | PAC50-CCA | Pressure type: Gauge pressure | Pressure unit: bar | Measuring range: 0 bar ... 6 bar | Accuracy: ≤ ± 1.5 %, of the span (including non-linearity, hysteresis, zero point and full scale error (corresponds to error of measurement as per IEC 61298-2)) | Process connection: PIF 4 mm + G ¼ | Process temperature: 0 °C ... +60 °C | Communication interface: - | Output signal: 2 x PNP/NPN/Push-Pull | Connection type: M12 round connector x 1, 4-pin, IP65, IP67 | Supply voltage: 17 V DC ... 30 V DC

    Medium
    Dry compressed air
    Pressure type
    Gauge pressure
    Pressure unit
    bar
    Measuring range
    0 bar ... 6 bar
    Overpressure safety
    15 bar
    Process temperature
    0 °C ... +60 °C
    Maximum ohmic load RA
    Optional, 4 mA ... 20 mA / 0 V… 10 V. Automatic detection depending on connected load or programmable. Output signals can be inverted: 20 mA ... 4 mA / 10 V ... 0 V, Load resistance for current output < 600 Ohm, Load resistance with current output > 3 kOhm
    Zero point adjustment
    Max. + 5 % of span
    Output signal
    2 x PNP/NPN/Push-Pull
    Diagnostics output
    Switching output 2 can be set as diagnostics output
    Display
    LCD with LED backlight (green/red), can be rotated electronically by 180°Pressure display: 4 digits, 16 segmentsPressure unit in display can be switched: bar, MPa, kPa, psi and inHgUpdate: 1,000, 500, 200, 100 ms (adjustable)
    Initialization time
    300 ms
    Communication interface
    -
    Process connection
    PIF 4 mm + G ¼1)
    Housing material
    Housing: polycarbonate, Buttons: TPE, DIN rail mounting: POM, seals: NBR
    Connection type
    M12 round connector x 1, 4-pin
    Supply voltage
    17 V DC ... 30 V DC
    Power consumption
    Max. 40 mA at L+= 24 VDC
    Electrical safety
    Protection class: IIIOvervoltage protection: 32 V DCShort-circuit protection: QA, Q1, Q2towards M and L+Reverse polarity protection: L+to M
    CE-conformity
    EMC directive: 2004/108/EC, EN 61326-2-3
    Weight sensor
    Approx. 40 g
    Enclosure rating
    IP652)IP672)
    Protection class III
    MTTF
    261.31 years
    Non-linearity
    ≤ ± 0.5 %, of span (Best Fit Straight Line, BFSL) according to IEC 61298-2
    Accuracy
    ≤ ± 1.5 %, of the span (including non-linearity, hysteresis, zero point and full scale error (corresponds to error of measurement as per IEC 61298-2))
    Setting accuracy of switching outputs
    ≤ ± 0.2 % of span
    Non-repeatability
    ≤ ± 0.2 % of the span
    Rated temperature range
    +10 °C ... +60 °C
    Ambient temperature, operation
    0 °C ... +60 °C
    Storage temperature
    –20 °C ... +80 °C
    Relative humidity
    ≤ 90 %
    Shock load
    Max. 30 g, xyz according to IEC 60068-2-27 (11 ms, mechanical shock)
    Vibration load
    Max. 5 g (10 ... 150 Hz), xyz, to DIN EN 60068-2-6
    EU declaration of conformity
    UK declaration of conformity
    ACMA declaration of conformity
    China RoHS
    ECLASS 5.0
    27200620
    ECLASS 5.1.4
    27200620
    ECLASS 6.0
    27200620
    ECLASS 6.2
    27200620
    ECLASS 7.0
    27200620
    ECLASS 8.0
    27200620
    ECLASS 8.1
    27200620
    ECLASS 9.0
    27200620
    ECLASS 10.0
    27200620
    ECLASS 11.0
    27200620
    ECLASS 12.0
    27200620
    ETIM 5.0
    EC000243
    ETIM 6.0
    EC000243
    ETIM 7.0
    EC000243
    ETIM 8.0
    EC000243
    UNSPSC 16.0901
    41112409
    Download Datasheet

    Manuals, CAD models, certificates and other materials are available on the manufacturer's website:

    Open product page on manufacturer's website